| AMBIENT OVERTEMP |
Ambient temperature higher than 114ºF |
Adjust dimmer room temperature |
| AMBIENT TEMP HIGH |
Ambient temperature higher than 104ºF |
Adjust dimmer room temperature |
| AMBIENT TEMP LOW |
Ambient temperature lower than 32ºF |
Adjust dimmer room temperature |
| BACKUP MISMATCH |
Backup look error |
Transfer correct backup look from another rack, or update to current looks. |
| CONFIG MISMATCH |
Configuration Error |
Transfer correct configuration from another rack |
| DATA ERROR PORT (A,B) |
Data transfer error on DMX512 port |
Check DMX512 port input cable and connector |
| DIMMER OVERTEMP |
One or more dimmers are overheated |
Check fans, intake, and exhaust for obstructions or adjust dimmer room temp. |
| ETCLINK FAILED |
ETCLink interface enabled but not responding |
Check all ETCLink cables and connectors |
| FREQUENCY ERROR |
Feed power frequency is not 50 or 60 Hz (+/- 1Hz) |
Check input frequency |
| NO AIRFLOW |
Insufficient airflow detected |
Check fans; check intake and exhaust for obstructions |
| NO DATA PORT (A,B) |
DMX512 port enabled, but no data received |
Confirm that DMX512 source device is turned on; check DMX512 port input cable and connector |
| OVERTEMP # |
Dimmer has overheated, shut down |
Press [Clear] to reset dimmer. If problem repeats, check airflow or replace dimmer module |
| PHASE (A,B,C) ERROR |
Phase voltage below 90V or above 140V |
Check line feed |
| PHASE (A,B,C) OFF |
All dimmers on phase off due to voltage error |
Check line feed |
| PHASE DETECT FAIL |
CEM Couldn't read phasing of incoming feed |
Replace CEM or check input power service |
| PROCESSOR FAIL |
CEM input/output processor not responding |
Replace CEM |
| SYSTEM ERROR |
System configuration data wrong or corrupted |
Replace CEM or check setup configuration |
| TEMP SENSOR STUCK |
Ambient temperature sensor is stuck |
Replace CEM |
| ZERO CROSSING ERROR |
CEM Hardware Failure |
Replace CEM |
The messages below are active in AF systems only
*These messages do not cause the beacon to flash |
| DC OUTPUT # |
DC component sent to load on dimmer |
Check devices on dimmer |
| DIM FAIL # |
Control signal sent to dimmer; no output detected |
Check dimmer's circuit breaker; replace power cube (SCR) |
| * LOAD CHANGE * |
Load has changed from recorded load |
Correct load or re-record |
| MOD. REMOVED # |
Dimmer removed from rack |
Reinstall dimmer module |
| * NO LOAD DIM # * |
Dimmer on, but no load on line |
Replace lamp |
| SCR FAIL |
SCR stuck on or off, or output stuck on |
Replace power cube (SCR) |